DefendX M32

128-Channel TCP/IP Fire Alarm Mimic and Event Recording Panel

A central network-based monitoring system designed to receive real-time status from up to 32 DefendX Nodes, operate 128 physical LED outputs, control 16 programmable relays, support multiple browser clients and retain at least 45 days of recorded status.

Specifications

Main Specifications

DefendX M32 main specifications
FeatureSpecification
Monitored fire panelsUp to 32
LED digital outputs128
Relay outputs16 changeover relays
Ethernet10/100 Mbps RJ45
CommunicationTCP/IP
Device protocolMQTT or structured TCP
Web clientsMinimum 25 simultaneous clients
Event retentionMinimum 45 days
Storage designMinimum 60-day capacity margin
Dashboard updateReal-time
Heartbeat supervisionSupported
Offline detectionTypically within 15 seconds
User rolesViewer, Operator and Administrator
Time synchronizationRTC and NTP
ReportingCSV and PDF
OperationLocal network, no compulsory cloud
DutyContinuous 24×7

128 LED outputs

  • 128 individually programmable outputs
  • Four outputs per fire alarm panel
  • Recommended mapping: Panel Power, Fire, Fault, Supervisory
  • Configurable steady or flashing operation
  • Lamp test
  • Acknowledged and unacknowledged behaviour
  • Flexible channel reassignment
  • Modular output cards

Concept Product Visualization

16 programmable relay outputs

All 16 relays can be configured for:

  • Common Fire
  • Common Fault
  • Common Supervisory
  • Panel power failure
  • Communication failure
  • Individual panel status
  • Building group status
  • BMS integration
  • CCTV triggering
  • External hooter or strobe
  • Custom cause-and-effect rules

Contact and timing options

  • NO, NC and COM contacts
  • Latched or non-latched operation
  • Activation delay
  • Restoration delay
  • Pulse or continuous operation
  • Normally energized fail-safe mode

Multi-client monitoring

One Controller. Many Synchronized Displays.

All clients view the same synchronized live status through a standard browser on the local network.

Main control room

Browser client

Security office

Browser client

Maintenance department

Browser client

Facility manager

Browser client

Tablet

Browser client

Large wall display

Browser client

45-day recording

The system records:

  • Fire activation and restoration
  • Fault activation and restoration
  • Supervisory activation and restoration
  • Panel power failure and restoration
  • Node online and offline status
  • Ethernet disconnection and restoration
  • LED output changes
  • Relay output changes
  • Alarm acknowledgment
  • Buzzer silence
  • Controller restart
  • User login
  • Configuration changes

Two recording methods

  1. 1. Immediate change-based event recording.
  2. 2. Configurable periodic complete status snapshots.
  1. 14:32:10FIRE ACTIVEP07Production Block

    NORMALACTIVE · acknowledged by Control Room Operator

  2. 14:32:11RELAY ACTIVATEDR01Common Fire Relay

    OFFON · acknowledged by System

  3. 14:32:15FIRE ACKNOWLEDGEDP07Production Block

    UNACKNOWLEDGEDACKNOWLEDGED · acknowledged by Control Room Operator

  4. 14:35:42COMMUNICATION LOSTP18Utility Building

    ONLINEOFFLINE · unacknowledged

Cause-and-effect programming

IF any panel reports Fire
THEN activate Common Fire Relay.
IF Panel 01 to Panel 08 reports Fire
THEN activate Building Group 1 Relay.
IF a Node remains offline for 15 seconds
THEN activate Communication Fault Relay.
IF panel power is absent for 10 seconds
THEN activate Panel Power Failure Relay.

Fail-safe behaviour

  • Offline status is never treated as Normal
  • Last valid data is marked as stale
  • Communication-fault relay can activate
  • Associated healthy indication turns off
  • Last received timestamp remains visible
  • Automatic reconnection
  • Full status resynchronization after reconnection

Historical playback

Reconstruct Any Moment in the Last 45 Days

Interactive simulation using demonstration data.

Reconstructed state at 14:32:10P07 Production Block: FIRE ACTIVE

R1 Common Fire · ACTIVER2 Common Fault · ACTIVER3 Common Supervisory · ACTIVER4 Communication Fault · NORMALR5 Panel Power Failure · NORMALR6 Building Group 1 Fire · NORMAL

Front panel

Local Indications and Controls

Indications

PowerSystem HealthyLAN HealthyCommon FireCommon FaultCommon SupervisoryCommunication FaultStorage Fault

Controls

Lamp TestAcknowledgeBuzzer SilenceReset

Front-panel controls operate the annunciation, buzzer and indication logic of the DefendX M32 only.

DefendX is intended as a supplementary monitoring, annunciation, event-recording and auxiliary output-control system. It does not replace the primary approved fire alarm control and indicating equipment. Final installation, interfacing and use must comply with applicable fire-safety regulations, project requirements and approvals.